Operate And Reset Level; 51Sef Time Delayed Sensitive Earth Fault; Reference - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.17 51SEF Time Delayed Sensitive Earth Fault

2.17.1 Reference

Parameter
Is
Setting
char
Characteristic setting
Tm
Time multiplier
t
Delay setting
d
t
Reset setting
res
Applied current (for
I
operate time)

2.17.2 Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
Variation
Unrestricted © 2013 Siemens Protection Devices Limited
Value
0.005, 0.006...1 xIn
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
1.0
0.00...20.00 s
DECAYING, 0, 1...60 s
IDMTL
2 to 20xIs
DTL
5 xIs
Value
105 % Is, ± 4 % or ± 1% In
³ 95 % I
± 1 %
£ 5 %
-10 °C to +55 °C
f
- 3 Hz
nom
to f
+ 2 Hz
nom
£ 5 %
harmonics to f
cutoff
7SR21 & 7SR22 Performance Specification
± 4 % or ± 1% In
op
Page 45 of 68