Power Protection; Power (32) - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR210 & 7SR220 Applications Guide
2.17

Power Protection

2.17.1 Power (32)

Parallel Busbar Feeder
If power is fed to a busbar through two parallel infeeds, then in the event of any fault on one of these infeeds it
should be selectively interrupted. This ensures a continued supply to the busbar through the remaining the
remaining infeed. For this purpose directional devises are needed which detect a shortcircuit current or a power
flow from the busbar in the direction of the infeed. Reverse-power protection can be set far below the rated power.
Motor Protection
An under power element protects against a loss of load condition by measuring the real power flow. This feature
provides an alternative to under current measurement as load loss may result in only a small change in current.
The under power output is initiated by a voltage element operating after a definite time delay. The applied power
setting will typically be 10-20% below minimum load, the power and time delay settings must take into account:
Where rated power cannot be reached during starting (for example where the motor is started with no
connected load) it may be necessary to inhibit this function for a set time. This feature requires a 52a
circuit breaker auxiliary contact mapped to an opto input to get the information CB Closed/CB Open.
Directional power measurement may operate on occurrence of a system power supply fail or system
fault. Power flow into the motor will reverse since the motor will act as a generator due to the inertia of
the connected load.
General Calculation
Real, apparent or reactive power is set in the relay as a multiple of the relay (or secondary) nominal
power where: -
Nominal relay power (secondary)
Example:
Nominal secondary apparent power (S):
Nominal 3-phase VA (secondary)
When calculating the required operate value in primary quantities the CT and VT ratios must be
considered i.e. where the above corresponds to a nominal primary 3-phase apparent power (S) of:
Nominal 3-phase VA (primary)
The primary nominal VA calculated above may not match that of the protected primary plant and so
settings should be adjusted accordingly.
Page 30 of 48
=
CT ratio
=
VT ratio
=
=
=
=
=
=
=
=
=
relay nominal current x relay nominal voltage.
400:1
33000:110
√3 x V
x I
L
L
√3 x 110 x 1
190.53 VA
1 xSn
√3 x V
x I
L
L
√3 x 330000 x 400
22.863 MVA
1 xSn
©2018 Siemens Protection Devices Limited

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents