7SR220 Settings Guide
Description
Hand Reset Outputs
Relays selected, as Hand Reset will remain latched until
manually reset from front panel or via communications link or
by removing DC Supply. By default relays are Self Resetting
and will reset when the driving signal is removed.
Min Operate Time 1
Minimum operate time of output relay if set to self reset, if also
set to be pulsed then this is the pulse width
Min Operate Time 2
Minimum operate time of output relay 2 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 3
Minimum operate time of output relay 3 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 4
Minimum operate time of output relay 4 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 5
Minimum operate time of output relay 5 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 6
Minimum operate time of output relay 6 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 7
Minimum operate time of output relay 7 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 8
Minimum operate time of output relay 8 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 9
Minimum operate time of output relay 9 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 10
Minimum operate time of output relay 10 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 11
Minimum operate time of output relay 11 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 12
Minimum operate time of output relay 12 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 13
Minimum operate time of output relay 13 if set to self reset, if
also set to be pulsed then this is the pulse width
Min Operate Time 14
Minimum operate time of output relay 14 if set to self reset, if
also set to be pulsed then this is the pulse width
Pickup Outputs
Selects which outputs can operate because a pickup condition
exists
Pulsed Outputs
Selects which outputs are pulsed. The pulse width is set by
the Min Operate Time setting for each output
3.13.3.

LED Config

Description
Unrestricted Page 100 of 107
Range
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12, 13, 14 )
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
0, 0.01 ... 59, 60
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12, 13, 14 )
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12, 13, 14 )
Range
© 2013 Siemens Protection Devices Limited
Default
--------------
0.1 s
0.1 s
0.1 s
0.1 s
0.1 s
0 s
0 s
0 s
0 s
0.1 s
0.1 s
0.1 s
0.1 s
0.1 s
--------------
--------------
Default