Led Config; Pickup Config - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR210 Settings Guide
3.8.3.

LED Config

Description
Self Reset LEDs
LEDs selected, as Self Reset will automatically reset when the
driving signal is removed. By default all LEDs are Hand Reset
and must be manually reset either locally via the front fascia or
remotely via communications.
PU Self Reset LEDs
LEDs selected, as Self Reset will automatically reset when the
driving signal is removed. By default all PU LEDs are Self
Reset.
Green LEDs
Selects which LEDs will be green when driven
Red LEDs
Selects which LEDs will be red when driven
PU Green LEDs
Selects which LEDs will be green when driven by a pickup
PU Red LEDs
Selects which LEDs will be red when driven by a pickup
3.8.4.

Pickup Config

Description
Gn P/F Pickups
When any of the selected pickups operate General Pickup is
driven.
Gn E/F Pickups
As Above
Gn SEF/REF Pickups
As Above
Gn Misc Pickups
As Above
Unrestricted Page 56 of 61
Range
Combination of ( 1 to 32)
Combination of ( 1 to 32)
Combination of ( 1 to 32)
Combination of ( 1 to 32)
Combination of ( 1 to 32)
Combination of ( 1 to 32)
Range
Combination of ( 51-1, 51-2, 50-1,
50-2 )
Combination of ( 51N-1, 51N-2,
50N-1, 50N-2, 51G-1, 51G-2, 50G-
1, 50G-2 )
Combination of ( 51SEF-1, 51SEF-
2, 50SEF-1, 50SEF-2, 64H )
Combination of ( 46IT, 46DT, 37-1,
37-2, 37G-1, 37G-2 )
© 2018 Siemens Protection Devices Limited
Default
--------
1 to 32
--------
1 to 32
1 to 32
1 to 32
Default
51-1, 51-2, 50-1,
50-2
51N-1, 51N-2,
50N-1, 50N-2,
51G-1, 51G-2,
50G-1, 50G-2
51SEF-1,
51SEF-2,
50SEF-1,
50SEF-2, 64H
46IT, 46DT, 37-
1, 37-2, 37G-1,
37G-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents