7SR210 & 7SR220 Description of Operation
4.8

Manual Control

A Manual Close Command can be initiated in one of three ways: via a Close CB binary input, via the data
communication Channel(s) or from the relay CONTROL MODE menu. It causes an instantaneous operation via
Manual Close CB binary output, over-riding any DAR sequence in progress.
Repeated Manual Closes are avoided by checking for Positive edge triggers. Even if the Manual Close input is
constantly energised the relay will only attempt one close.
A Manual Close will initiate Line Check if Line Check Trip is enabled. If a fault appears on the line during the
Close Pulse or during the Reclaim Time with Line Check enabled, the relay will initiate a Trip and Lockout. This
prevents a CB being repeatedly closed onto a faulted line. Where Line Check Trip = DELAYED then
instantaneous protection is inhibited until the reclaim time has elapsed.
Manual Close resets Lockout, if the conditions that caused Lockout have reset, i.e. there is no trip or Lockout
input present.
Manual Close cannot proceed if there is a Lockout input present.
With the Autoreclose function set to Disabled the Manual Close control is still active.
Close CB Delay
The Close CB Delay is applicable to manual CB close commands received through a Close CB binary input or
via the Control Menu. Operation of the Manual Close CB binary output is delayed by the Close CB Delay
setting. The status of this delay is displayed on the relay fascia as it decrements towards zero. Only when the
delay reaches zero will the close command be issued and related functionality initiated.
Blocked Close Delay
The close command may be delayed by a Block Close CB signal applied to a binary input. This causes the
feature to pause before it issues the CB close command and can be used, for example, to delay CB closure until
the CB energy has reached an acceptable level. If the Block signal has not been removed before the end of the
defined time, Blocked Close Delay, the relay will go to the lockout state. The output Close CB Blocked
indicates this condition.
Open CB Delay
The Open CB Delay setting is applicable to CB trip commands received through an Open CB binary input or via
the Control Menu. Operation of the Open CB binary output is delayed by the Open CB Delay setting. The status
of this delay is displayed on the relay fascia as it decrements towards zero. Only when the delay reaches zero will
the trip command be issued and related functionality initiated.
It should be noted that a CB trip initiated by an Open CB command is fundamentally different from a CB trip
initiated by a protection function. A CB trip caused by a CB Open command will not initiate functionality such as
2
circuit-breaker fail, fault data storage, I
t measurement and operation counter.
CB Controls Latched
CB controls for manually closing and tripping can be latched for extra security.
With Reset operation, the control resets when the binary input drops off. This can lead to multiple control restarts
due to bounce on the binary input signal.
With Latch operation, the close or trip sequence always continues to completion (or sequence failure) and bounce
on the binary input is ignored.
Reset operation can be useful, however, as it allows a close or trip sequence to be aborted by dropping off the
binary input signal.