Instantaneous Overcurrent Protection (50); Figure 3.1.2-1 Logic Diagram: Instantaneous Over-Current Element - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

3.1.2

Instantaneous Overcurrent Protection (50)

Two instantaneous overcurrent elements are provided in the 7SR21 relay. Four elements are provided in the
7SR22 e.g. giving the option of using two elements set to forward and two to reverse.
Each instantaneous element (50-n) has independent settings. 50-n Setting for pick-up current and 50-n Delay
follower time delay. The instantaneous elements have transient free operation.
Where directional elements are present the direction of operation can be set using 50-n Dir. Control setting.
Directional logic is provided independently for each 50-n element.
Operation of the instantaneous overcurrent elements can be inhibited from:
Inhibit 50-n
79 P/F Inst Trips: 50-n
50-n Inrush Action: Inhibit
50-n VTS Action: Inhibit
Figure 3.1.2-1
Unrestricted ©2018 Siemens Protection Devices Limited
A binary input, virtual input, function key or remote data Comms.
When 'delayed' trips only are allowed in the auto-reclose sequence
(79 P/F Prot'n Trip n = Delayed).
Operation of the inrush current detector function.
Operation of the VT Supervision function (7SR22).
Logic Diagram: Instantaneous Over-current Element
7SR210 & 7SR220 Description of Operation
Page 27 of 94