Siemens Argus 7SR21 Technical Manual page 564

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR210 & 7SR220 Commissioning & Maintenance Guide
Op. Time
27/59
DTL
D.O.
P.U.
D.O
2x Vs (OV)
Phase
setting
U/O
Hyst.
Tolerence
(sec)
(calculated)
Volts
Volts
0.5x Vs
(Volts)
(UV)
V
(V
)
4
x
1.1.1.1
Element Blocking
The Vx Under/Over Voltage elements can be blocked by Binary Input Inhibit and VT Supervision. This
functionality should be checked.
Element
BI Inhibits
VT Supervision
27/59x
Check correct indication, trip output, alarm contacts, waveform record.
Page 52 of 82
© 2013 Siemens Protection Devices Limited