Siemens Argus 7SR21 Technical Manual page 138

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR210 Settings Guide
3.4.4.
Measured E/F
Description
Gn 51G/50G Measurement
Selects whether the RMS value used by the 51G & 50G
elements is True RMS or only calculated at fundamental
frequency
3.4.4.1.
51G-1
Description
Gn 51G-1 Element
Selects whether the 51G-1 IDMTL measured Earth Fault
element is enabled
Gn 51G-1 Setting
Pickup level
Gn 51G-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Gn 51G-1 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
Gn 51G-1 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
Gn 51G-1 Min Operate Time
Minimum operate time of element.
Gn 51G-1 Follower DTL
Additional definite time added after characteristic time
Gn 51G-1 Reset
Selects between an ANSI decaying reset characteristic or DTL
reset
Gn 51G-1 Inrush Action
Selects if the 51G-1 element is blocked from operating when
2nd Harmonic Inrush Detector operates
3.4.4.2.
51G-2
Description
Gn 51G-2 Element
Selects whether the 51G-2 IDMTL measured Earth Fault
element is enabled
Gn 51G-2 Setting
Pickup level
Gn 51G-2 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Gn 51G-2 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
Gn 51G-2 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
Gn 51G-2 Min Operate Time
Minimum operate time of element.
Gn 51G-2 Follower DTL
Additional definite time added after characteristic time
Gn 51G-2 Reset
Selects between an ANSI decaying reset characteristic or DTL
reset
Unrestricted Page 14 of 61
Range
RMS, Fundamental
Range
Disabled, Enabled
0.005, 0.006 ... 0.995, 1
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
(ANSI) Decaying, 0 ... 59, 60
Off, Inhibit
Range
Disabled, Enabled
0.005, 0.006 ... 0.995, 1
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
(ANSI) Decaying, 0 ... 59, 60
© 2018 Siemens Protection Devices Limited
Default
RMS
Default
Disabled
0.5 xIn
IEC-NI
1
5 s
0 s
0 s
0 s
Off
Default
Disabled
0.5 xIn
IEC-NI
1
5 s
0 s
0 s
0 s