Arc Flash Detection (50Afd) - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.1

Arc Flash Detection (50AFD)

I
L1
(I
)
A
I
L2
(I
)
B
I
L3
(I
)
C
I
4
(I
)
G
I
5
(I
)
SEF
V
L1
(V
)
A
V
L2
(V
)
B
V
L3
(V
)
C
V
4
(V
)
X
Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:
The overcurrent level can be tested without an arc flash by separately energising or inverting the arc detector
binary input continuously for the duration of the test for the zone being tested.
If the current setting is low, gradually increase current until element operates.
If the current level required is greater than the thermal limit of the relay, apply 0.9x setting, check for no operation,
apply 1.1x setting, check operation.
Optical sensors such as 7XG31 can be tested by application of a suitable light source. Relay instrumentation can
be used to indicate binary input pickup or by the 50AFD Zone-n Flash outputs.
The 7XG31 devices will typically require 10000 lx light level for 1.25ms to trigger. A high powered photographic
flash is the most convenient means of initiating positive sensor operation.
Note that mobile phone or small compact camera flashes may not have sufficient power to cause sensor
operation but may be suitable if held directly against the sensor.
Check correct indication, trip output, alarm contacts, waveform record.
© 2013 Siemens Protection Devices Limited
60
37
50
49
CTS-
(x2)
BF
60
37
50
49
CTS-
(x2)
BF
60
37
50
49
CTS-
(x2)
BF
46
46
60
NPS
BC
CTS
(x2)
50
37
BF
50
37
BF
NOTE: The use of some
functions are mutually exclusive
27
59
(x4)
27
47
81
59
(x2)
(x6)
(x4)
27
59
(x4)
27
59
Figure 2.1-1
N/A
I
(I
), I
(I
), I
(I
L1
A
L2
B
L3
C
49, 50, 51
50AFD Zone-n Flash - Hand Reset, 50AFD Zone-n – Hand/self Reset
7SR210 & 7SR220 Commissioning & Maintenance Guide
67/
50
21
51V
50/51
AFD
LB
I
(x4)
67/
50
21
51V
50/51
AFD
LB
(x4)
I
67/
50
21
51V
50/51
AFD
LB
(x4)
I
67/
60
50/51N
VTS
(x4)
67/
50/51G
(x4)
67/
64
50/51S
H
(x4)
32
32S
74
TCS
59N
(x2)
79
25
Arc Flash Detection
),
81
51c
HBL
2/5
81
51c
HBL
2/5
81
51c
HBL
2/5
81
51c
HBL
2/5N
37G
(x2)
37S
(x2)
55
21FL
Optional
Page 25 of 82