Siemens Argus 7SR21 Technical Manual page 261

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR220 Settings Guide
Description
E14
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
E14 Pick-up Delay
Time before equation output operates, after equation satisfied
E14 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
E14 Counter Target
Select number of times equation must be satisfied before
equation output operates
E14 Counter Reset Mode
Select type of counter reset mode
E14 Counter Reset Time
Select counter reset time
E15 Equation
Enable or Disable logic equation E15
E15
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
E15 Pick-up Delay
Time before equation output operates, after equation satisfied
E15 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
E15 Counter Target
Select number of times equation must be satisfied before
equation output operates
E15 Counter Reset Mode
Select type of counter reset mode
E15 Counter Reset Time
Select counter reset time
E16 Equation
Enable or Disable logic equation E16
Unrestricted Page 56 of 107
Range
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
© 2013 Siemens Protection Devices Limited
Default
0 s
0 s
1
Off
0 s
Disabled
0 s
0 s
1
Off
0 s
Disabled