7SR220 Technical Manual

2.2 USB Interface (COM2)

The USB communication port is connected using a standard USB cable with a type B connection to the relay and
type A to the PC.
The PC will require a suitable USB driver to be installed; this will be carried out automatically when the Reydisp
software is installed. When the Reydisp software is running with the USB cable connected to a device an additional
connection is shown. Connections to these devices are not shown when they are not connected.
The USB communication interface on the relay is labelled Com 2 and its associated settings are located in the Data
communications menu. When connecting to Reydisp using this connection the default settings can be used without
the need to first change any settings.
Access to the communication settings for the USB port is only available from the relay front fascia via the key pad
setting menu COMMUNICATIONS MENU.
Setting Name
OFF
IEC60870-5-103
COM2-USB
MODBUS-RTU
Protocol
ASCII
DNP3
COM2-USB
0 - 254 for IEC60870-5-103
Station
1 - 247 for Modbus RTU
Address
0 - 65534 for DNP3.0
Local
COM2-USB
Local or Remote
Mode
Remote
USB Type A
Socket on PC

2.3 RS485 Interface (COM1)

The 2-wire RS485 communication port is located on the rear of the relay and can be connected using a suitable
RS485 120 Ohm screened twisted pair cable.
Chapter 4 - Page 8 of 96
Range/Options
Local Engineer Access
Fig. 2-1 Communication to Front USB Port
Default
Setting
IEC60870-5-103
0
Local
USB Type B
Socket on Device
© 2017 Siemens Protection Devices Limited
Notes
Reydisp
software requires
IEC60870-5-103.
An address within the
range of the relevant
protocol must be
given to identify the
relay. Each relay in a
network must have a
unique address.
Refer to
Appendix
1, page 95, for
further explanation