7SR210 Settings Guide
3.7.2.
Binary Input Config (Variants may differ)
Description
Inverted Inputs
Selects which inputs pickup when voltage is removed.
BI 1 Pick-up Delay
Delay on pickup of DC Binary Input 1
BI 1 Drop-off Delay
Delay on dropoff of DC Binary Input 1
-
BI 39 Pick-up Delay
Delay on pickup of DC Binary Input 9
BI 39 Drop-off Delay
Delay on dropoff of DC Binary Input 9
Enabled In Local
Selects which inputs are enabled when the relay is in
Operating Mode 'Local' or 'Local Or Remote'
Enabled In Remote
Selects which inputs are enabled when the relay is in
Operating Mode 'Remote' or 'Local Or Remote'
Unrestricted Page 40 of 61
Range
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9 )
0, 0.005 ... 14300, 14400
0, 0.005 ... 14300, 14400
0, 0.005 ... 14300, 14400
0, 0.005 ... 14300, 14400
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9 )
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9 )
© 2018 Siemens Protection Devices Limited
Default
---------
0.02 s
0 s
0.02 s
0 s
1, 2, 3, 4, 5, 6, 7,
8, 9
1, 2, 3, 4, 5, 6, 7,
8, 9