Section 4: Control Functions; Check Synchronising; Reference; Live/Dead Line/Bus Detector Elements - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR21 & 7SR22 Performance Specification

Section 4: Control Functions

4.1

Check Synchronising

4.1.1

Reference

Parameter
V
Nominal Voltage
nom
f
Nominal Frequency
n
V
Live Setting
live
V
Dead Setting
dead
V
Line Voltage Setting
sl
V
Bus Voltage Setting
sb
V
Voltage Differential Setting
diff
Θ
CS Angle
cs
Θ
SS Angle
ss
f
COZ Slip
coz
f
CS Slip Freq
cs
f
SS Slip Freq
ss
t
CS Timer
cs
t
SS Timer
ss
f
Split Slip
sps
t
/t
DLC/DBC Delays
dlc
dbc
t
Sync Close Window
cw
4.1.2

Live/Dead Line/Bus Detector Elements

Attribute
V
Live operate level
live,act
Live reset level
V
Dead operate level
dead,act
Dead reset level
Repeatability
Variation
Unrestricted Page 66 of 68
Value
100 % V
V
dead,act
100 % V
V
live,act
± 1 %
-10 °C to +55 °C
£ 5 %
£ 1 %
f
± 5 %
nom
Value
40-160 V
50/60 Hz
10 % - 150 %
10 % - 150 %
10 % - 150 %
10 % - 150 %
5 % - 95 %
1 – 90 º
1 – 90 º
30 mHz – 250 mHz
20 mHz – 250 mHz
10 mHz – 250 mHz
0-100 s
0-1 s
20 mHz – 250 mHz
0-60 s
1 s – 1200 s
, ± 1 % V
live
n
, ± 1 % V
n
, ± 1 % V
dead
n
, ± 1 % V
n
© 2013 Siemens Protection Devices Limited