Afd Arc Flash Detector; (Refer To 7Xg31 Technical Manual For Performance Characteristics); Reference; Operate And Reset Level - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.25 50 AFD ARC Flash Detector

(Refer to 7XG31 Technical Manual for performance characteristics)

2.25.1 Reference

Parameter
50 AFD
Setting

2.25.2 Operate and Reset Level

Attribute
I
Operate level
op
Transient overreach (X/R £ 100)
Reset level
Repeatability

2.25.3 Operate and Reset Time

Attribute
t
50AFD Overcurrent operate time
basic
t
AFD Zone operate time (Flash & 50AFD)
op
Repeatability
Disengaging time
Unrestricted © 2013 Siemens Protection Devices Limited
7SR21 & 7SR22 Performance Specification
Value
1, 2,...10 xIn
Value
100 % Is, ± 10 %
£ -30 %
³ 95 % I
op
± 5 %
Value
10 ms – 16 ms
15 ms – 25 ms
± 10 ms
< 50 ms
Page 55 of 68