7SR21 & 7SR22 Performance Specification
2.17.3 Operate and Reset Time
Attribute
Starter operate time
t
Operate time
op
Reset time
Repeatability
Overshoot time
Disengaging time
Variation
Figure 2-2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2-3 and
Figure 2-4 show the ANSI operate and reset curves. These operate times apply to non-directional characteristics.
Where directional control is applied then the directional element operate time should be added to give total
maximum operating time.
Unrestricted Page 46 of 68
Value
20 ms, ± 20 ms
t
op
char = IEC-NI,
IEC-VI,
IEC-EI,
for char =
IEC-LTI
t
op
char = ANSI-MI,
ANSI-VI,
ANSI-EI,
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
, ± 1 % or ± t
char = DTL
t
d
t
res
char = ANSI and
t
= DECAYING
res
for char = ANSI-MI : R = 4.85
¹ DECAYING
t
t
res
res
± 1 % or ± 20 ms
< 40 ms
< 50 ms
f
- 3 Hz
nom
to f
+ 2 Hz
nom
£ 5 %
harmonics to f
cutoff
K
=
´
Tm
, ± 5 % or ± 30 ms,
[ ]
a
I
-
1
Is
IEC-NI : K = 0.14, a = 0.02
IEC-VI : K = 13.5, a = 1.0
IEC-EI : K = 80.0, a = 2.0
IEC-LTI : K = 120.0, a = 1.0
é
ù
A
ê
ú
=
+
´
, ± 5 % or ± 30 ms,
B
Tm
[ ]
ê
ú
P
I
-
1
ë
û
Is
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2,
cycle
R
=
´
Tm
, ± 5 % or ± 30 ms,
[ ]
2
-
1
I
Is
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
, ± 1 % or ± 20 ms
© 2013 Siemens Protection Devices Limited
B = 0.1217, P = 2.0