3.15 Voltage Protection: Neutral Overvoltage (59N) – 7SR22
Two Neutral Overvoltage (or Neutral Voltage Displacement) elements are provided in the 7SR22 relay.
59N Voltage Source setting selects the source of the residual voltage to be measured. The voltage is measured
directly from the Vx input or derived from the line voltages where suitable VT connections are present. The relay
utilises fundamental voltage measurement values for this function.
One of the elements can be configured to be either definite time lag (DTL) or inverse definite minimum time
(IDMT).
The Neutral Inverse Time Lag 59NIT Setting sets the pick-up voltage level (3V
An inverse definite minimum time (IDMT) can be selected using 59NIT Char. A time multiplier is applied to the
characteristic curves using the 59NIT Time Mult setting (M): -
Alternatively, a definite time lag delay (DTL) can be chosen using 59NITChar. When Delay (DTL) is selected the
time multiplier is not applied and the 59NIT Delay (DTL) setting is used instead.
An instantaneous or definite time delayed reset can be applied using the 59NIT Reset setting.
The second element has a DTL characteristic. The Neutral Definite Time Lag 59NDT Setting sets the pick-up
voltage (3V
) and 59NDT Delay the follower time delay.
0
Operation of the neutral overvoltage elements can be inhibited from:
Inhibit 59NIT
Inhibit59NDT
It should be noted that neutral voltage displacement can only be applied to VT arrangements that allow zero
sequence flux to flow in the core i.e. a 5-limb VT or 3 single phase VTs. The VT primary winding neutral must be
earthed to allow the flow of zero sequence current.
Unrestricted Page 52 of 94
=
t
op
A binary or virtual input, function key or remote data Comms.
A binary or virtual input, function key or remote data Comms.

Figure 3.15-1 Logic Diagram: Neutral Overvoltage Element

é
ù
M
s
ê
ú
[
]
-
3Vo
1
ë
û
Vs
©2018 Siemens Protection Devices Limited