2.3
32 Power
2.3.1
Reference
Parameter
Ss
32-n Setting
t
32-n Delay setting
d
2.3.2
Operate and Reset Level
Attribute
S
Operate level
op
Reset level
Variation
2.3.3
Operate and Reset Time
Attribute
Element basic
t
basic
operate time
t
Operate time following delay
op
Disengaging time
2.3.4
Operate Threshold
Attribute
Minimum levels for
operation
Unrestricted © 2013 Siemens Protection Devices Limited
Over-power
Under-power
-10 °C to +55 °C
+ 2 Hz £ 5 %
f
– 3 Hz to f
nom
nom
Over-power
Under-power
I
V
7SR21 & 7SR22 Performance Specification
Value
0.05...2 x Sn
0.00 ... 14400 s
Value
100 % Ss, ± 5% or ± 2% Sn
³ 95 % S
op
£ 105 % S
op
£ 5 %
Value
1.1 x Ss: 60 ms ± 10 ms
2.0 x Ss: 45 ms ± 10ms
0.5 x Ss: 30 ms ± 10ms
, ± 1 % or ± 10ms
t
+ t
basic
d
< 40 ms
Value
2.5 % In
2.5% Vn