Siemens Argus 7SR21 Technical Manual page 153

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

Description
E8
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed
(requires E1 to drive L11 in output matrix)E1 =
F3^L11
E8 Pickup Delay
Time before equation output operates, after equation satisfied
E8 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
E8 Counter Target
Select number of times equation must be satisfied before equation
output operates
E8 Counter Reset Mode
Select type of counter reset mode
E8 Counter Reset Time
Select counter reset time
E9 Equation
Enable or Disable logic equation E9
E9
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed
(requires E1 to drive L11 in output matrix)E1 =
F3^L11
E9 Pickup Delay
Time before equation output operates, after equation satisfied
E9 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
E9 Counter Target
Select number of times equation must be satisfied before equation
output operates
E9 Counter Reset Mode
Select type of counter reset mode
E9 Counter Reset Time
Select counter reset time
E10 Equation
Enable or Disable logic equation E10
E10
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed
(requires E1 to drive L11 in output matrix)E1 =
F3^L11
Unrestricted ©2018 Siemens Protection Devices Limited
Range
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
(20 Character String)
7SR210 Settings Guide
Default
0 s
0 s
1
Off
0 s
Disabled
0 s
0 s
1
Off
0 s
Disabled
Page 29 of 61