Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
Point
Description
Index
59
Active Power C
60 P (3P)
61 Reactive Power A
62 Reactive Power B
63 Reactive Power C
64 Q (3P)
65 Apparent Power A
66 Apparent Power B
67 Apparent Power C
68 S (3P)
71 Power Factor A
72 Power Factor B
73 Power Factor C
74 Power Factor(3P)
75 Act Energy Exp
76 Act Energy Imp
77 React Energy Exp
78 React Energy Imp
81 Thermal Status Ph A
82 Thermal Status Ph B
83 Thermal Status Ph C
95 Active Setting Group
99 Vab Secondary
100 Vbc Secondary
101 Vca Secondary
102 Vn Primary
103 Vn Secondary
105 Vx Primary
106 Vx Secondary
108 I Phase A Max
109 I Phase B Max
110 I Phase C Max
111 P 3P Max
© 2017 Siemens Protection Devices Limited
Chapter 4 - Data Communications Definitions
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Default
Default
Change Event
Variation
Variation
Assigned Class
Static
(1, 2, 3 or none)
Object 30
Object 32
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
1
0,3
1
0,3
1
0,3
1
0,1
4
0,1
4
0,1
4
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
0,3
2
Default
Default
Event
Multiplier
4
0.000
4
0.000
4
0.000
4
0.000
4
0.000
4
0.000
4
0.000
4
0.000
4
0.000
4
0.000
4
1000.000
4
1000.000
4
1000.000
4
1000.000
3
1.000
3
1.000
3
1.000
3
1.000
4
100.000
4
100.000
4
100.000
4
1.000
4
10.000
4
10.000
4
10.000
4
0.010
4
10.000
4
0.010
4
10.000
4
1.000
4
1.000
4
1.000
4
0.000
Chapter 4 - Page 81 of 96
Default
Deadband
1000000.000
1000000.000
1000000.000
1000000.000
1000000.000
1000000.000
1000000.000
1000000.000
1000000.000
1000000.000
0.100
0.100
0.100
0.100
Disabled
Disabled
Disabled
Disabled
1.000
1.000
1.000
1.000
1.000
1.000
1.000
100.000
1.000
100.000
1.000
100.000
100.000
100.000
1000000.000