Siemens Argus 7SR21 Technical Manual page 639

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

5.10.2 Design View
5.10.2.1
Load Blinder 3Ph
The 3-phase load blinder has the following setting parameters:
21LB – 3P Angle +ve
21LB – 3P Angle -ve
21LB – 3P Impedance
21LB – 3P VPPS
21LB – 3P INPS
The design of Load Blinder 3Ph takes into consideration that the protection blocking should only be issued during
definable allowable system power flow conditions i.e. an overcurrent blocking signal can only be issued when:
a.
Positive Sequence Voltage Vpps is not significantly reduced i.e. is above the 21LB-3P VPPS Setting.
AND
b.
Negative Sequence Current Inps is lower than 21LB-3P INPS Setting
AND
c.
The impedance measured in all phases is within the operate zone.
Zpps is calculated from Vpps and Ipps. The calculated Zpps is used to determine if the impedance is in
the operate zone i.e. greater than the 21LB-3P Impedance setting and less than the 21LB-3P Angle
settings. Suitable settings can be chosen to provide overcurrent blocking in the forward or reverse
directions.
© 2013 Siemens Protection Devices Limited
Figure 5.10.2.1-1 Logic Diagram 3 Phase
7SR210 & 7SR220 Applications Guide
Page 45 of 48