37Sef Undercurrent; Reference; Operate And Reset Level - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR21 & 7SR22 Performance Specification
2.6
37G & 37SEF Undercurrent
2.6.1

Reference

Parameter
Is
Setting
t
Delay setting
d
2.6.2

Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
Variation
2.6.3
Operate and Reset Time
Attribute
t
Element basic operate time
basic
t
Operate time following delay
op
Repeatability
Overshoot time
Disengaging time
Unrestricted Page 26 of 68
-10 °C to +55 °C
+ 2 Hz £ 5 %
f
- 3 Hz to f
nom
nom
Value
0.005, 0.10...5.0 xIn
0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010...
10000, 10100... 14400 s
Value
100 % Is, ± 5 % or ± 1% In
£ 105 % I
± 0.1 % In
or I
op
op
± 1 %
£ 5 %
Value
1.1 to 0.5 xIs: 35 ms, ± 10 ms
, ± 1 % or ± 10 ms
t
+ t
basic
d
± 1 % or ± 10 ms
< 40 ms
< 60 ms
© 2013 Siemens Protection Devices Limited