Additional Settings - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
Point
Description
Index
185 CB Wear B
186 CB Wear C
187 CB Wear A Remaining
188 CB Wear B Remaining
189 CB Wear C Remaining
190 CB Wear Minimum
191 Fault Distance Perunit
196 Frequency Max
197 S 3P Max
318 Sec Active Power A
319 Sec Active Power B
320 Sec Active Power C
321 Sec P (3P)
322 Sec Reactive Power A
323 Sec Reactive Power B
324 Sec Reactive Power C
325 Sec Q (3P)
326 Sec Apparent Power A
327 Sec Apparent Power B
328 Sec Apparent Power C
329 Sec S (3P)
330 CB Trip Time Meter
337 PF 3P Max

5.4 Additional Settings

The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name
Unsolicited
DISABLED, ENABLED
Mode
© 2017 Siemens Protection Devices Limited
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Default
Change Event
Assigned Class
(1, 2, 3 or none)
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
Range/Options
Chapter 4 - Data Communications Definitions
Default
Default
Variation
Variation
Default
Static
Event
Multiplier
Object 30
Object 32
1
3
1
3
1
3
1
3
1
3
1
3
5
7
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
Default
Setting
DISABLED
As Required
Default
Deadband
0.000
1000000.000
0.000
1000000.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
0.001
1.000
100.000
1.000
0.000
1000000.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1.000
10.000
1000.000
0.010
1000.000
0.100
Notes
Setting is only visible
when any port
Protocol is set to
DNP3.