Description
E16
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
E16 Pick-up Delay
Time before equation output operates, after equation satisfied
E16 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
E16 Counter Target
Select number of times equation must be satisfied before
equation output operates
E16 Counter Reset Mode
Select type of counter reset mode
E16 Counter Reset Time
Select counter reset time
E16 Equation
Enable or Disable logic equation E16
Unrestricted ©2018 Siemens Protection Devices Limited
Range
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
7SR220 Settings Guide
Default
0 s
0 s
1
Off
0 s
Disabled
Page 57 of 107