Current Protection: High Impedance Restricted Earth Fault (64H); Figure 3.6-1 Logic Diagram: High Impedance Ref (64H) - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

3.6
Current Protection: High Impedance Restricted Earth
Fault (64H)
One high impedance Restricted Earth Fault (REF) element is provided.
The relay utilises fundamental current measurement values for this function.
The single phase current input is derived from the residual output of line/neutral CTs connected in parallel. An
external stabilising resistor must be connected in series with this input to ensure that this element provides a high
impedance path.
64H Current Setting sets the pick-up current level. An output is given after elapse of the 64H Delay setting.
External components – a series stabilising resistor and a non-linear resistor – are used with this function. See
'Applications Guide' for advice in specifying suitable component values.
Operation of the high impedance element can be inhibited from: -
Inhibit 64H
Unrestricted ©2018 Siemens Protection Devices Limited
A binary or virtual input, function key or remote data Comms

Figure 3.6-1 Logic Diagram: High Impedance REF (64H)

7SR210 & 7SR220 Description of Operation
Page 43 of 94

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents