2.2.2

Front Fascia without Flag Output

Figure 2-2
2.3

Power Supply Unit (PSU)

The relay is supplied with the following nominal power supply ranges:
60 V to 240 V AC/DC power supply (BI threshold - 88 V AC/DC)
24 V to 60 V DC power supply (BI threshold -19 V DC)
The power supply module is equipped with 2 or 4 binary inputs and binary outputs based on the ordering options.
The PSU also consists of one RS485 communication interface (half duplex) for communicating with RTUs and
parameterization of relays via remote locations.
For AC connections, the auxiliary supply is made with the live connection to positive terminal and neutral
connection to negative for consistency and safety.
If the power supply voltage levels are falling below the relay minimum operate level, the 7SR45 Argus relay power
will automatically switch over to CT power through phase CT currents.