To read the content value in the addresses 0x0000 and 0x0001 inside DVP15MC11T via
function code 03. 0x0000 and 0x0001 are the Modbus address of %MW0 and %MW1 inside
DVP15MC11T respectively. Suppose that the value of %MW0 is 0x0100 and the value
of %MW1 is 0x0200.
Request message: 00 00 00 00 00 06 01 03 00 00 00 02
Response message: 00 00 00 00 00 07 01 03 04 01 00 02 00
Function code: 06 to write one single word register value
Request message data structure:
Byte NO.
B-4
Byte NO.
The number of read word registers.
Byte8
(Counted by Byte)
Byte9
The content value in a word register
Byte10
...
The content value in a word register
Byte n
Byte0
Transaction identifier
Byte1
Byte2
Protocol identifier
Byte3
Byte4
Modbus data length
Byte5
Byte6
Modbus ID
Byte7