DVP15MC11T Operation Manual
8.15.3
ImmediateInput
FB/FC
FC
ImmediateInput is used for the immediate refresh of input points.
Parameters
Parameter name
Input
Num
Input
Num
Note:
The symbol ● indicates that the parameter is allowed to connect to the variable or constant of the data type.
Function Explanation
The ImmediateInput instruction is used for refreshing external input point status to %IX0.0~%IX0.15.
If the ImmediateInput instruction does not exist, the controller refreshes external input point status
to %IX0.0~%IX0.15 once only every time the program scan starts.
_8
The Input parameter value 0~15 corresponds to %IX0.0~%IX0.15. Num represents the quantity of
consecutive devices starting from the one specified by Input. E.g. when Input value is 0 and Num is
2, it indicates that the external input point status is refreshed to %IX0.0 and %IX0.1.
Precautions for Correct Use
The instruction is only used for the immediate refresh of local input points instead of extension input
points.
8-210
Input/
Meaning
Output
Start input point
Input
Number
Input
Bit string
●
Explanation
ImmediateInput
EN
E NO
In put
Num
Description
Start input point
Number of input points for
immediate refresh
Integer
●
Applicable
model
DVP15MC11T
Valid range
0~15
1~16
Real
Time, date
number