8.6

Timer Instructions

8.6.1

TON

FB/FC
FB
TON is used for the ON delay.
Parameters
Parameter
name
In
Timer input
PT
Set time
Q
Timer output
ET
Elapsed time
 T#0ns ~ 213503d23h34m33s709ms551us615ns
In
PT
Q
ET
_8
Note:
The symbol ● indicates that the parameter is allowed to connect to the variable or constant of the data type.
Function Explanation
The TON instruction is defined as the function of a timer for the ON delay.
When In is TRUE, the timer starts to measure the time and the value of ET increases accordingly.
When ET equals PT, Q is TRUE. When In is set to FALSE, the measuring of the time stops and Q
and ET are both reset.
Precautions for Correct Use
When the output value of ET reaches the set value of PT, the timer stops measuring time. ET is reset to 0
(0ns) when In changes from TRUE to FALSE.
8-40
Input/
Meaning
Output
Input
Input
Output
Output
Bit string
Explanation
TO N_in st ance
TON
EN
E NO
In
Q
PT
ET
Description
Controls the timer to start or reset
Time from when the timer starts until Q
changes to TRUE.
Q is TRUE when the set time PT is
reached.
Elapsed time from the time when the timer
starts to current time.
Integer
Applicable
model
DVP15MC11T
Valid range
TRUE or FALSE
TRUE or FALSE
Real
Time, date
number