DVP15MC11T Operation Manual
LED state
Red light single
flash
12
1
Red light ON
ERR LED: Red light is in a single flash and double flashes as below.
ON
Red light
single flash
OFF
Red light
double flashes
 CAN2 (Motion) LED
RUN LED
LED state
LED OFF
Green light
blinking
12-4
Explanation
The bus error is out of the alert
level.
Bus-off
200m s
1000ms
ON
200m s
200m s
2 00ms
OFF
Explanation
No axis is configured for
CAN2 (Motion) port in the
software.
Not all of the axes configured
for CAN2 (Motion) in the
software have been online.
How to deal with
4. Check if the interference around CANopen
bus cable is too strong.
1. Check if the CANopen bus cable connection
is correct.
2. Check if the CANopen bus cable is Delta
standard cable.
3. Check if the two ends of CANopen bus have
connected a terminal resistor respectively.
4. Check if the baud rate of CANopen port is
the same as that of other slaves.
5. Check if the interference around CANopen
bus cable is too strong.
1. Check if the bus cable wiring in CANopen
network is correct.
2. The baud rates of DVP15MC11T and other
stations are same.
10 00ms
How to deal with
Configure the slave connected to Motion port to
the master in the software.
1.
Check if the bus cable connection in the
Motion network is correct.
2.
Check if the Motion bus cable is Delta
standard CANopen cable.
3.
Check if the two ends of Motion bus have
connected a terminal resistor respectively
4.
Check if the baud rates of Motion port and
slaves are same.
5.
Check if the slaves configrued in the
software have actually been connected to