Wiring Schematic 5: Multi-Signal Module Inputs
Dry normally-closed
contacts at source
equipment or line
pressure switches
+
COM
SIGNAL 1
+
COM
SIGNAL 2
+
COM
SIGNAL 3
+
COM
SIGNAL 4
+
COM
SIGNAL 5
Multi-Signal Module front panel
50
6-847718-00 Rev. B00
"M" OR "R" Module
Pin 10
Pin 1
Multi-Signal Module
at FIRST master alarm panel
NOTE:
Field wiring cable shields must be grounded at
only one end, inside alarm panel back box. Refer
to page 39 for details.
Pin 10
20 wire
ribbon cable
to adjacent
module
Multi-Signal Module
at SECOND master alarm panel
SIGNAL 1 - pin 1 (+), pin 2 (COM)
SIGNAL 2 - pin 3 (+), pin 4 (COM)
SIGNAL 3 - pin 5 (+), pin 6 (COM)
SIGNAL 4 - pin 7 (+), pin 8 (COM)
SIGNAL 5 - pin 9 (+), pin 10 (COM)
CAUTION:
Do not connect TotalAlert 2 master/combo alarm
to switch/relay contacts connected to any alarm
panels other than those listed below:
•
TotalAlert 2
•
MEGA2
•
MEGA
Pin 1
20 wire
ribbon cable
to adjacent
module