General technical data
A.3
Mechanical and climatic conditions for operation
Ambient operating
conditions
Where the
modules should
not be used
Climatic
conditions
A-4
The bus connectors and RS 485 repeaters described in this manual are
designed for stationary use in sheltered locations. Ambient operating
conditions to IEC 1131-2.
Unless additional protective measures are implemented, the bus connectors
and RS 485 repeaters should not be used:
where they would be exposed to a high proportion of ionizing radiation
where operating conditions are harsh, for example due to:
– dust
– aggressive vapors or gases
in systems which require special monitoring, for example:
– elevators
– electrical systems in high-risk zones
Installation in cabinets counts as an additional protective measure.
The bus connectors and RS 485 repeaters are suitable for use under the
following climatic conditions:
Ambient
conditions
Temperature
from 0 to 60 C
Relative
from 5 to 95 %
humidity
Barometric
from 1080 to 795 hPa
pressure
Pollutant
SO
: < 0.5 ppm;
2
concentration
Relative humidity (RH) <
60 %, no condensation
H
S: < 0.1 ppm;
2
Relative humidity (RH) <
60 %, no condensation
Ranges
without condensation,
corresponds to relative humidity
(RH) category 2 to IEC 1131-2
corresponds to an altitude from
-1000 to 2000 m
Test:
10 ppm; 4 days
Test:
1 ppm; 4 days
ET 200 Distributed I/O System
Remarks
EWA 4NEB 780 6000-02a