8.4
Mechanical and Climatic Ambient Conditions
Climatic environmental conditions
The following climatic environmental conditions apply:
Ambient conditions
Temperature
Rate of temperature change
Relative humidity
Air pressure
Contaminant concentration
Note
Modules for the extended operating range from 0 to 55 °C / 50 °C for vertical installation
A series of ET 200S modules is approved for an extended operating range from 0 to 55 °C or
from 0 to 50 °C for vertical installation.
Refer to the "Properties" in the relevant manuals for the ET 200S modules to find out
whether a module is approved for the extended operating range.
Note
Any supply or load voltage for the ET 200S may not exceed 24 VDC. This voltage limit must
be ensured.
ET 200S
Operating Instructions, 08/2008, A5E00515771-06
Areas of application
between 0 and 60°C
From 0 to 40 °C
10 K/h
From 15 to a maximum of 95%
from 1080 hPa to 795 hPa
SO
: < 0.5 ppm;
2
rel. humidity < 60 %, no condensation
H
S: < 0.1 ppm;
2
rel. humidity < 60 %, no condensation
ISA-S71.04 serverity level G1; G2; G3
General technical specifications
8.4 Mechanical and Climatic Ambient Conditions
Remarks
for horizontal installation
for all other mounting positions
Without condensation
Corresponds to an altitude of -1000 m
to 2000 m
Check:
10 ppm; 4 days
1 ppm; 4 days
—