IM 308-C master interface and memory card
3.3
Installing the IM 308-C
Setting the
jumpers
Slots in the
S5-115U system
Table 3-7
Slots in the S5-115U system
CR 700-2 module rack:
PS
CPU
CR 700-3 module rack:
PS
CPU
3-8
You must set jumper X10 on the IM 308-C. Jumper X10 enables you to
configure bus segments in such a way that they are not grounded:
If you want to operate the SINEC L2 DP as grounded, set the jumper to
position "1–2".
If you want to operate the SINEC L2–DP as non-grounded, set the
jumper to position "2–3".
The tables below will show you how to set jumper X9. The position
depends on where the IM 308-C master interface is to be inserted.
The tables below show you where to insert the IM 308-C in the rack. The
gray hatching indicates the slots where you can insert the IM 308-C.
Table 3-6
Slots in the S5-115U system, CR 700-0 module rack
CR 700-0 module rack:
PS
CPU
0
1
2
0
1
2
0
1
2
3
4
5
3
4
5
ET 200 Distributed I/O System
3
IM
6
IM
6
IM
EWA 4NEB 780 6000-02a