6.6
Connecting the voltage supply
Cable type
For the 24 V DC voltage supply, use flexible cables with a cross-section from
0.25 mm
Rules for routing
See Section 5.1 for details on cable routing (DC voltage
cables
Connecting the
To connect the power supply of the RS 485 repeater:
power supply
1. Slacken screws "M" and "PE".
2. Strip the ends of the 24 V DC cable conductors.
3. Connect the cable to the terminals marked "L+", "M" and "PE".
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
RS 485 repeaters: installing, connecting and operating
2
2
to 2.5 mm
(AWG 26 to 14).
60 V, unshielded).
6-11
6