Assigning Station Numbers - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

IM 308-C – addressing, diagnostics and use of the FB IM308C
9.6

Assigning station numbers

Application
No application
Assigning station
numbers
9-22
For some DP standard slaves you set the station number by means of the
software, e.g. for the ET 200C distributed I/O station or the DP/AS-I Link.
Note that the FB IM308C can be used to change the station numbers of DP
standard slaves only.
DP slaves whose station number can only be set by means of switches set in
the housing, or DP Siemens slaves: you cannot assign the station numbers by
means of the software.
To assign a station number to a DP slave, proceed as follows:
1. Configure the parameterization master IM 308-C and the DP standard
slave with the new station number using COM ET 200 Windows.
Tip: Use the highest possible baud rate for the DP standard slave.
2. Connect the bus to the IM 308-C and to the target DP slave which is to
receive a station number.
3. Connect the PG to the AS 511 interface of the CPU and set up a
configuration as shown in Fig. 9-2 :
CPU
Figure 9-2
Using the FB IM308C to assign a station number to a DP slave
4. Switch the IM 308-C to STOP.
5. Start the STEP 5 program.
IM 308-C
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Et 200

Table of Contents