IM 308-C – addressing, diagnostics and use of the FB IM308C
Options for
addressing
Table 9-1 Modes of addressing with the IM 308-C as DP master
Addressing
Address
1
range
Linear
(F)F000
to
H
P area
(F)F0FF
H
Linear
(F)F100
to
H
Q area
(F)F1FF
H
P page
(F)F0C0
to
H
(F)F0FE
H
Q page
(F)F100
to
H
(F)F1FE
H
DP window (F)F800
to
H
(F)F9FF
(de-
H
fault)
(F)FA00
to
H
(F)FBFF
H
(F)FC00
to
H
(F)FDFF
H
(F)FE00
to
H
(F)FFFF
**
H
** S5-135U and S5-155U only.
1
Column indicates the address area of the IM 308-C for addressing. In the 945, 946/947 and 948 CPUs, this address
is on memory page F.
2
The 13300 bytes represent the maximum addressing volume – even if you use linear and page addressing in parallel.
9-4
Your options for addressing the distributed I/O system are as follows:
linear addressing (P and Q areas)
page addressing (P and Q areas)
or
function block FB IM308C (FB 192).
Table 9-1 shows the inputs and outputs at your disposal and the applicable
modes of addressing.
Access
Page
through ...
selection
address
PY 0 to
PY 255
QB 0 to
QB 255
PY 192 to
PY 255 /
PY 254
(F)F0FF
QB 0 to
QB 255 /
QB 254
(F)F1FF
FB IM308C
(FB 192)
Max.
inputs / outputs
256 bytes for inputs /
If an output can be
256 bytes for outputs
addressed in linear mode,
it
it cannot be addressed
256 bytes for inputs /
through the FB IM308C.
256 bytes for outputs
per IM 308-C:
If an output is addressed
16 pages, 63 bytes =
through pages, it cannot
1008 bytes for inputs /
be addressed through the
1008 bytes for outputs
FB IM308C. Station
numbers 120 through 123
max. 16 IM 308-C:
are not available
16128 bytes / 16128
bytes
per IM 308-C:
If an output is addressed
16 pages, 255 bytes =
through pages, it cannot
4080 bytes for inputs /
be addressed through the
4080 bytes for outputs
FB IM308C. Station
numbers 120 through 123
max. 16 IM 308-C:
are not available
65280 bytes / 65280
bytes
13300 bytes in all for in-
2
puts and outputs.