Meanings Of The Error Numbers In The Err Parameter - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

IM 308-C – addressing, diagnostics and use of the FB IM308C
Error numbers in
the ERR parameter
Table 9-20 Meanings of the error numbers in the ERR parameter
LOW byte
of ERR
Hex.
Dec.
00
000
No error occurred
H
A1
161
Illegal CPU, FB IM308C not
H
executable in this CPU
A2
162
Number of the IM 308-C is invalid
H
(IMST parameter)
A3
163
Invalid station number of the DP
H
slave (IMST parameter)
A4
164
LENG parameter invalid
H
A5
165
TYP parameter invalid
H
A6
166
GCGR parameter invalid
H
A7
167
TYP parameter invalid; the S marker
H
memory area is valid only for the
following CPUs:
CPU 945
CPU 928B
CPU 946/947 and CPU 948
A8
168
TYP parameter invalid; the extended
H
data block area is valid only for the
following CPUs:
CPU 945
CPU 928A, CPU 928B
CPU 946/947 and CPU 948
A9
169
TYP parameter invalid; specified
H
data block DB/DX does not exist.
AA
170
TYP parameter invalid; specified
H
data block DB/DX is too small.
9-34
Table 9-20 shows the meanings of the ERR parameter.
Meaning
Use the FB IM308C from the S5ETxxST.S5D file which
belongs to the CPU (see Table 9-12).
The number of the IM 308-C must be one of the following
values: 0, 16, 32, 48, 64, 80, 96, 112, 128, 144, 160, 176,
192, 208, 224 or 240.
The station number must be within the range 1 to 123.
The LENG parameter must be either "–1" (joker length) or in
the range 1 to 244 or 4 to 244, depending on the function.
The parameter value must be in the range 0 to 3.
The low byte of the GCGR parameter must be a value not
equal to 0.
Select a different memory area, e.g. marker M.
Select a different memory area, e.g. data block DB.
Create the specified source/target data block.
The specified source/target data block must exist in the
application memory and must be long enough:
Remedy
LENG
–1:
Minimum length (words) = STAD + LENG/2 – 1
LENG = 1:
Minimum length depends on the configuration of the DP
slave;
STAD
Minimum length (words)
ET 200 Distributed I/O System
STAD + 122
EWA 4NEB 780 6000-02a