Technical Data Of The Rs 485 Repeater - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

RS 485 repeaters: installing, connecting and operating
Technical data
6-4
The table below shows the technical data of the RS 485 repeater:
Table 6-4

Technical data of the RS 485 repeater

Technical data
Power supply
Rated voltage
Ripple
Current consumption at rated voltage
No consumer via PG/OP interface
Consumer via PG/OP interface (5 V/90 mA)
C
Consumer via PG/OP interface (24 V/100 mA)
i PG/OP i t f
Galvanic isolation
Connection of wave guides
Redundancy
Baud rate
Degree of protection
Dimensions W
H
D (in mm)
Weight (including packaging)
Note
There is a special RS 285 repeater with degree of protection IP 65 for use in
harsh industrial environments and an RS 485 repeater for redundant opera-
tion.
For a detailed description of these RS 485 repeaters, see SINEC L2/L2FO
Network Components.
24 V DC
18 V DC to 30 V DC
100 mA
130 mA
(24 V/100 A)
200 mA
200 A
yes, AC 500 V
yes, via repeater adapters
no
9.6 kbaud to 12 Mbaud
IP 20
45
350 g
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
128
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Et 200