Siemens SIMATIC S5 Manual page 67

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Design and method of operation of the S5-95U with DP master interface
Table 4-4 Technical data of the S5-95U with DP master interface, continued
Technical data
Special SINEC L2 DP data
Number of S5-95Us as DP
masters on the SINEC L2 DP
Number of DP slaves per S5-95U
as DP master
Baud rates
Address volume for
SINEC L2-DP
Integrated organization blocks
Integrated function blocks
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
max. 124 DP masters
max. 16 DP slaves
9.6 kbaud to 1.5 Mbaud
128 bytes for outputs
128 bytes for inputs
2 bytes overview diagnostics
OB 1, OB 3, OB 13, OB 21, OB 22,
OB 31, OB 34, OB 251
FB 230, FB 240, FB 241, FB 242,
FB 243, FB 250, FB 251
4
4-9

Hide quick links:

Advertisement