12.1 General technical specifications
Table 12-10 Disturbance via supply lines to EN 55016: Limit Class A, Group 1
from 0.15 to 0.5 MHz
from 0.5 to 5 MHz
from 5 to 30 MHz
See also
http://support.automation.siemens.com/cs
view/59193566)
12.1.4

Shipping and storage conditions

Transport and storage of modules
The described components fulfill the requirements of IEC 61131 Part 2 with regard to transport
and storage conditions. The following specifications apply for modules that are transported or
stored in their product packaging.
Table 12-11 Transport and storage conditions
Type of condition
Free fall (in product packaging)
Temperature
Atmospheric pressure
Relative humidity
Sinusoidal oscillations to
IEC 60068-2-6
Impact to IEC 60068-2-27
12.1.5

Mechanical and climatic ambient conditions for operation

Conditions of use
The described components are designed for use in a fixed, non-sheltered location. The
operating conditions exceed the requirements of IEC 61131 Part 2.
160
< 79 dB (μV)Q
< 66 dB (μV)M
< 73 dB (μV)Q
< 60 dB (μV)M
< 73 dB (μV)Q
< 60 dB (μV)M
(http://support.industry.siemens.com/cs/ww/en/
Permitted range
≤0.3 m
From ‑40 °C to + 70 °C
From 1080 hPa to 606 hPa
(corresponding to a height of ‑1000 m to 4000 m)
From 5% to 95%, non-condensing
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2