General technical data
A.1
Electromagnetic compatibility
Definition
Pulse interference
Table A-1 Electromagnetic compatibility with regard to pulse interference
Pulse interference
Electrostatic discharge to
IEC 801-2 (DIN VDE 0843, Part 2)
IEC 801 2 (DIN VDE 0843 P t 2)
Burst pulses
(rapid, transient interference) to IEC
801-4 (DIN VDE 0843, Part 4)
Single high-energy pulse (surge) to IEC
801-5
(DIN VDE 0839, Part 10)
Assymetric link
Symmetric link
Sinusoidal
interference
RF emissions
A-2
Electromagnetic compatibility (EMC) is the ability of an electrical device to
function satisfactorily in its electromagnetic environment without affecting
this environment.
The bus connectors and the RS 485 repeaters described in this manual
comply with the statutory requirements for EMC.
The details of interference immunity and RFI suppression are listed below.
Table A-1 lists the details of electromagnetic compatibility with regard to
pulse interference.
8 kV
4 kV
2 kV (feeder line)
2 kV (signal line)
2 kV (feeder line)
2 kV (signal line/data line)
1 kV (feeder line)
1 kV (signal line/data line)
RF interference (external electromagnetic fields) to IEC 801-3
(DIN VDE 0843, Part 3): tested with 10 V/m in the range from 80 MHz to
1000 MHz (corresponding to severity 3).
RFI suppression to EN 55011: Limit class A, Group 1.
Tested with
ET 200 Distributed I/O System
Corresponding to
severity
3 (air discharge)
2 (contact discharge)
3
3
EWA 4NEB 780 6000-02a