Table 8-5 Meanings of the master parameters (IM 308-C), continued
Designation
Response
Response monitoring enables you to define how the DP slave reacts to a DP master
monitoring for
error or a break in the data traffic on the bus.
slaves
If the DP slave is not addressed within the response monitoring time you define, the
slave goes to safe condition (all outputs are set to "0").
If you set response monitoring to "Yes" (by checking the box), the setting applies to
all DP slaves assigned to the DP master. Note, however, that you can switch off
response monitoring for individual DP slaves, for example during initial operation
(switch in the "Slave parameters" dialog box).
!
See Section 11.2 for a detailed description of response monitoring.
Entering master
To enter the master parameters:
parameters
1. Select Configure
2. Enter the master parameters. Click on the "Help" button to obtain
3. Confirm the master parameter settings and close the dialog box by
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
Meaning
Danger
If you switch off response monitoring, there is a possibility that
the outputs of a particular slave may not be set to "0" if an error
occurs.
Consequently, we strongly recommend that response
monitoring be switched off only for initial operation.
Master parameters
or
double-click on the icon for the DP master.
Result: The "Master parameters" dialog box is opened.
context-sensitive help on the master parameters.
pressing the "OK" button.
Default
Yes
8
8-13