D-1 Overvoltage-Protection Components For Coarse Protection - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Additional
If the measures outlined above cannot be implemented, it is essential to
measures
provide coarse protection at the 0
lightning diverters. The table below is an overview of the components you
can use for this purpose.
Table D-1 Overvoltage-protection components for coarse protection
Ser.
Lines for ...
No.
1
Three-phase TN-C system
Three-phase TN-S and TT systems
Alternating current TN-L, TN-S-,
TT systems
2
24 V DC supply
3
SINEC L2 bus line
4
Inputs/outputs of digital modules
24 V DC
110/220 V AC
Inputs/outputs of analog modules
up to
12 V
up to
24 V
up to
48 V
1
Order components directly from: DEHN + Soehne, Elektrotechnische Fabrik, Hans-Dehn-Str. 1, D-92318 Neumarkt,
Germany
2
Order numbers as per catalog Service XV 10. The order number of this catalog is E89700-S1034-X-A3.
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
The ET 200 distributed I/O system and lightning protection
1 interface in the form of suitable
... install the following at the 0
interface:
3 pcs. DEHNport lightning diverter,
phases L1/L2/L3 to PEN
4 pcs. DEHNport lightning diverter,
phases L1/L2/L3/N to PE
2 pcs. DEHNport lightning diverter,
phases L1+, N to PE
1 pc. Blitzductor KT, Type AD 24 V
up to 500 kbaud: 1 pc. Blitzductor
KT, Type ARE 8 V
over 500 kbaud: 1 pc. Blitzductor KT,
Type AHFD 5 V
1 pc. Blitzductor KT, Type AD 24 V
2 pc. DEHNguard 150 overvoltage
diverter
1 pc. Blitzductor KT, Type ALE 15 V
1 pc. Blitzductor KT, Type ALE 48 V
1 pc. Blitzductor KT, Type ALE 60 V
1
Order No.
1
900 100
1
900 100
1
900 100
2
DSN: 919 253
2
DSN: 919 232
2
DSN: 919 270
2
DSN: 919 253
1
900 603
2
DSN: 919 220
2
DSN: 919 227
2
DSN: 919 222
D-5