Entering Slave Parameters - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Parameterizing, saving and documenting the configuration with COM ET 200 Windows
8.2.4

Entering slave parameters

Definition
Meanings of the
slave parameters
Table 8-6 Meanings of the slave parameters
Designation
Family
Family of the distributed I/O station, e.g. ET 200B, ET 200C, ... .
Station type
Enter the station type of the DP slave as shown, for example, by the order number or
the label on the DP slave.
Designation
Enter a name for the distributed I/O station; max. length 40 characters.
Response
You can switch response monitoring on or off for each individual slave.
monitoring
monitoring
!
See Section 11.2 for a detailed description of response monitoring.
Error-reporting
You can switch the error-reporting mode PEU or QVZ on or off for each slave. The
switch for setting the error-reporting mode for all slaves assigned to a DP master is in
the "Master parameters" dialog box.
See Section 11.2 for a detailed description of the PEU, QVZ and "none" options for
the error-reporting mode.
!
8-14
The slave parameters enable you to define:
the family and type of the slave
the name of the slave
the configuration and corresponding addresses of the slave (Configure ...)
the structure of a parameterization telegram, if necessary
(Parameterize ...), and
whether or not the error-reporting mode selected for the DP master or
response monitoring is to be switched off for this DP slave.
The meanings of the individual slave parameters are shown in Table 8-6.
Meaning
Danger
If you switch off response monitoring, there is a possibility that
the outputs of a particular slave may not be set to "0" if an error
occurs.
Consequently, we strongly recommend that response monitoring
be switched off only for initial operation.
Caution
If you set the error-reporting mode to "none", diagnosis with the
FB IM308C is the only way that you can detect an error in the
distributed I/O system from within the application program.
Consequently, we strongly recommend that response monitoring
be switched off only for initial operation.
Default
Yes
QVZ
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a