Reductions
The following configuration options are available in the Reductions section.
•
Gradient limit (adjustment rate):
If the power company requires a reduction, it has to be configured in this box. (Enter the values in
seconds)
•
Max. cos(phi) inductive/under excited and max. cos(phi) capacitive/over-excited:
A maximum shift factor can be defined wit this the reduction. With this, it can be that less reactive
power is fed-in into the grid than what the characteristic curve allows in the partial load range in
order to maintain the shift factor limits.
Note!
Entering zero as the value deactivates the particular limit.
Configuration Menu