AO Module Specifications

Total Number of Outputs
Output Arrangement
D to A Resolution
Output Accuracy
Temperature Stability
Internal Settling Time
Output Load
Crosstalk Rejection
Interference Suppression
Output Protection
Diagnostic LEDs
User Connection
Cable and TB Holder
Module Replacement
Isolation
Insulation
Operating Voltage
Power Consumption
Dimensions
Weight
4 AO current (0-20 mA) or voltage (0-10 V)
Isolated floating channels, each channel can be connected as
0-20 mA or 0-10 V DC voltage
14 bit
±0.05% full scale @ 25ºC
25 PPM/ºC
Max. 1.0 msec
Voltage: > 1.0 kΩ, < 1.0 µf
750 Ω (internal power source)
Current:
<
Better than 50 dB between any pair of outputs
Common mode rejection > 60 dB
Voltage output: short circuit current, max. 30 mA
Current output: No-load voltage max. 22 V DC
Module error LED, Voltage mode LED, Current mode LED,
Calibration LED per channel
2 Terminal Blocks (3.5mm pitch), Maximum 18 AWG
20-wire cable braid with Terminal Block holder connector, 26 AWG
Hot swap replacement– module extraction/insertion under voltage
1.5 kV between output and module logic
Insulation resistance 100 MΩ @ 500 V DC, per IEC60255-5
10.8-16 V DC and 3.3 V DC (from the motherboard connector)
Refer to Appendix D: ACE3600 Maximum Power Ratings.
37 mm W x 225 mm H x 180 mm D, (1.5" W x 8.7" H x 7.1" D)
Approx. 0.29 Kg (0.64 Lb)
Specifications subject to change without notice.