I/O Connection Diagram - Motorola ACE3600 RTU Owner's Manual

Programmable remote terminal unit
Hide thumbs Also See for ACE3600 RTU:
Table of Contents

Advertisement

I/O Connection Diagram

Connection of a dry contact sensor to the DI module requires "wetting" the contact with a
voltage. This can be done using the 24V DC floating plug-in power supplies that can be added
to the module (in 16/32 DI Fast 24V/ Fast 24V IEC TYPE 2 modules only). The 24V can be
also used to power "wet" sensors.
External
Wetting
Source
External
Wetting
Source
Dry Contact
Sensor
+
"Wet"
Sensor
-
Dry Contact
Sensor
+
-
+
+
"Wet"
Sensor
-
-
DI Module
DIx (input x)
COM (common)
DI Module
DIx (input x)
COM (common)
DI Module
DIx (input x)
+24V (Plug-in PS)
DI Module
+24V (Plug-in PS)
DIx (input x)
COM (common)
6-10
Digital Input Module