Note: For the 8 I/O slots option and the 19" frame metal back option, the brackets for wall
mount installation are included and need not be ordered separately.
Procedure 2-4 How to Mount the RTU 19" Frame Metal Back on a Wall
1) Remove the CPU, Power Supply and I/O modules from the RTU frame.
2) Drill four holes into the wall at the horizontal and vertical distances shown in Figure 2-10.
(If you choose to further secure the 19" frame, drill four additional four holes, at the
distances shown in Figure 2-10.)
3) Using two M5 screws (not supplied), secure the rectangular wall mounting bracket
(07013022001 from kit FHN7419A) to the wall, as shown in Figure 2-11. Repeat for the
second bracket.
Figure 2-11 19" Frame Metal Back Bracket Installation
4) Fit the metal frame in between the two brackets, lining up the holes on the sides. (See
Figure 2-12.)
5) Using three supplied M4 screws, secure the left bracket to the left side of the frame. (See
Figure 2-12.) Using three more screws, secure the right bracket to the right side of the
frame.
6) If you choose to further secure the 19" frame, screw two additional M5 screws (not
supplied) into the two middle holes on the left bracket, as shown in Figure 2-12. Repeat
for the right bracket.
2-10
Installation