The initial screen is as follows:
MDS iNET 900
Starting Information Screen
-==================================================================-
Device Mode:
Device Name:
Network Name:
IP Address:
Device Status:
Uptime:
Firmware Version:
Hardware Version:
Serial Number:
Press 'G' to go to Main Menu
1.
Press 'G' and the Main Menu will be displayed.
2.
Press 'B' and the Network Configuration Menu will be displayed.
3.
Press 'G' for IP Address configuration.
4.
In the IP Address Configuration Menu, press 'B' to set the Static IP Address to
169.254.0.12.
5.
Next press 'C' to set the Static IP subnet mask to 255.255.0.0. It is recommended that all
units having the same AP (Access Point) be on the same subnet mask.
Note that the Static (sub)Net Mask and Static IP Gateway addresses should be the same
as those of the IP Gateway and EPIB. Their IP Address should be on the same subnet.
For example 169.254.0.100 for an IP Gateway address of 169.254.0.012 is suitable.
Also note that when using PPP it is recommended to have the IP Address of PPP on the
same subnet, for example 169.254.0.13. See Configuring for PPP below.
6.
Press 'E' to commit changes. Press ESC to return to the Network Configuration Menu.
7.
Finally press 'D' and enter the maximum number of remotes. By default this value is 50.
If the AP has more than that, you must change the value.
Access Point
AP Demo Set I
Demo Set l
169.254.0.12
Operational
01 hrs, 51 min
4.4.0
1.0.3
1069975
21-71