Figure 21-12 RTU Site Configuration for MDLC over ASTRO IV&D – Port Type Parameters
Advanced Parameter Configuration
Figure 21-13 RTU Site Configuration for MDLC over ASTRO IV&D – Advanced Parameters
Generally no other changes are required to Advanced Physical or Link Layer parameters. For
information on these parameters, see the MDLC over IP chapter of the ACE3600 STS
Advanced Features manual.
Procedure 21-12 How to Configure the Advanced Parameters of the ACE3600 Port for the
Astro XTS2500 IV&D Digital Radio
1.
(ASTRO System 6.3-6.5 only) Make sure that the Advanced Link parameter Registration
life time to 28800 seconds (default) in order to restart the radio periodically.
2.
If any changes are required, click on the appropriate screen in the Port Tab.
3.
Change the settings as necessary.
Note: The Default Group ID Address should be left 000.000.000. The actual values will
be read by the RTU from the radio upon connection.
4.
Save any changes.
5.
Save the project.
21-22